Operating conditions
1. Ambient temperature: upper limit +40℃, lower limit -30℃; Days difference does not exceed 32K;
2. Altitude: 1000m and the following areas;
3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s);
4. Air pollution level: IV class
5. Earthquake intensity: do not exceed 8 degree;
6. Ice thickness: no more than 10mm.
Technical data
| Item |
Unit |
Parameter |
| Voltage, current parameters |
|
|
| Rated voltage |
kV |
40.5 |
| Rated short time power frequency withstand voltage (1min) |
kV |
95 |
| Rated lightning impulse withstand voltage (peak) |
kV |
185 |
| Rated current |
A |
1250, 1600, 2000 |
| Rated short-circuit breaking current |
kA |
25, 31.5 |
| Rated operating sequence |
|
O-0.3s-CO-180s-CO |
| Rated short-circuit current breaking times |
Times |
12 |
| Rated short-circuit closing current (peak) |
kA |
63, 80 |
| Rated peak withstand current |
kA |
63, 80 |
| Rated short-time withstand current |
kA |
25, 31.5 |
| Rated short-circuit current duration |
S |
4 |
| Average opening velocity |
ms |
1.5±0.2 |
| Average closing speed |
ms |
0.7±0.2 |
| Contact closing bounce time |
ms |
≤5 |
| Three-phase close (open) synchronization error |
ms |
≤2 |
| Closing time |
ms |
≤150 |
| Opening time |
ms |
≤60 |
| Mechanical life |
Times |
10000 |
| Rated operational voltage and auxiliary circuits rated voltage |
V |
DC220, AC220 |
| DC resistance of circle every phase (not including transformer) |
μΩ |
≤100 |
| Dynamic, static contact allowed to wear thickness |
mm |
3 |
| Weight |
kg |
800 |
Overall and mounting dimensions(mm)
The ZW7-40.5 shape and size of installation
Installation base diagram