Home Categories Send inquiry

ZW32Y-12 Outdoor Vacuum Circuit Breaker

Selection

Operating conditions

1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude: ≤2000m; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃ .

Technical data

Item Unit Parameter
Rated voltage kV 12
Rated insulation level 1min power frequency withstand voltage Dry test  Wet test kV 42/ fracture 48
kV 34
Lightning impulse withstand voltage (peak) kV 75/ fracture 85
Rated current A 630, 1250
Rated short-circuit breaking current kA 20
Rated short-circuit breaking current time Times 30
Rated short-circuit closing current (peak) kA 50
Rated peak withstand current kA 50
Rated short-time withstand current kA 20
Rated short circuit duration S 4
Opening time ms <50
Closing time ms <60
Full off time ms ≤100
Arcing time ms ≤50
Mechanical life Times 30000
Switch on power J 70
Rated operational voltage and auxiliary circuits rated voltage V DC 220
V AC 220

Overall and mounting dimensions(mm)

Circuit breaker and mounting dimensions Controller outline and mounting dimensions

ZW32Y-12 Outdoor Vacuum Circuit Breaker Related Video: