Selection
Operating conditions
1. Ambient temperature: upper limit +40℃, lower limit -30℃;
2. Altitude: ≤2000m;
3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s);
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution grade: III class;
6. Maximum daily temperature variety less than 25℃ .
Technical data
| Item | Unit | Parameter | 
| Rated voltage | kV | 12 | 
| Rated insulation level | 1min power frequency withstand voltage | Dry test  Wet test | kV | 42/ fracture 48 | 
| kV | 34 | 
| Lightning impulse withstand voltage (peak) | kV | 75/ fracture 85 | 
| Rated current | A | 630, 1250 | 
| Rated short-circuit breaking current | kA | 20 | 
| Rated short-circuit breaking current time | Times | 30 | 
| Rated short-circuit closing current (peak) | kA | 50 | 
| Rated peak withstand current | kA | 50 | 
| Rated short-time withstand current | kA | 20 | 
| Rated short circuit duration | S | 4 | 
| Opening time | ms | <50 | 
| Closing time | ms | <60 | 
| Full off time | ms | ≤100 | 
| Arcing time | ms | ≤50 | 
| Mechanical life | Times | 30000 | 
| Switch on power | J | 70 | 
| Rated operational voltage and auxiliary circuits rated voltage | V | DC 220 | 
| V | AC 220 | 
Overall and mounting dimensions(mm)
Circuit breaker and mounting dimensions
Controller outline and mounting dimensions