Selection
Operating conditions
1. Altitude≤2000 meters
2. The environment temperature: -30℃ ~+55℃ outdoor; the highest annual average temperature 20 ℃, the highest daily average temperature 30 ℃;
3. Relative humidity: 95% (25℃)
4. Seismic capacity: horizontal ground acceleration 0.3g, vertical ground acceleration 0.15g, at the same time duration of three sine waves, a safety factor of 1.67
5. Earthquake intensity: 7 degrees
6. The maximum daily temperature difference: 25 ℃
7. The intensity of sunshine (wind speed 0.5m/s): 0.1W/cm²
8. The maximum wind speed: 34m/s
9. The maximum ice thickness: 10mm
10.Installation position: outdoor, the 10kV overheadline responsibility demarcation point
11.Grounding: neutral non grounding, arc suppression coil grounding and low resistance grounding.
Technical data
Item |
Unit |
Parameter |
Voltage, current parameters |
|
|
Rated voltage |
KV |
12 |
Insulation level of fracture |
The power frequency (dry and wet test) |
KV |
48 |
Lightning impulse test voltage (peak) |
KV |
85 |
On the ground and interphase insulation level |
Power frequency |
Dry test |
KV |
42 |
Wet test |
KV |
34 |
Lightning impulse test voltage (peak) |
KV |
75 |
Rated current |
A |
630 |
Rated short-circuit breaking current |
kA |
16, 20, 25 |
Rated short-circuit breaking current interruption times |
Times |
30 |
Rated short-time withstand current |
kA |
16, 20, 25 |
Rated short circuit duration |
S |
4 |
Rated short-circuit close current (peak) |
kA |
40, 50, 63 |
Rated peak withstand current |
kA |
40, 50, 63 |
Mechanical life |
Times |
> 10000 |
Rated current on and off times |
Times |
10000 |
Net weight |
kg |
180 |
Mechanical properties |
|
|
Clearance between open contacts |
mm |
9 |
+1 |
-0.5 |
Contact overtravel |
mm |
3 |
+1 |
-0.5 |
Opening speed |
m/s |
1.2±0.2 |
Closing speed |
m/s |
0.6±0.2 |
Contact closing jump time |
ms |
≤2 |
pjase spacing |
mm |
280±2 |
External charged air insulation distance |
mm |
235±2 |
External creepage distance |
cm/kV |
3.8 |
Three phase opening different period |
ms |
≤2 |
Each phase conductive loop resistance |
μΩ |
≤150 |
Closing time |
ms |
20~60 |
Opening time |
ms |
18~45 |
The energy storage motor rated power |
W |
≯40 |
The energy storage motor rated voltage |
V |
AC220 |
Rated closing operating voltage |
V |
AC220 |
Maximum / minimum closing operating voltage |
V |
AC264/143 |
Rated opening operation voltage |
V |
AC220 |
Maximum / minimum voltage of motor |
V |
AC264/143 |
Maximum / minimum opening operating voltage |
V |
AC242/187 |
Ratecl pressure SF6 gas (gauge) |
MPa |
"0" |
Overall and mounting dimensions(mm)