ZN28-12 Indoor Vacuum Circuit Breaker

Selection

Operating conditions

1. The environment temperature: upper limit +40℃, lower limit -15℃; 2. Altitude: ≤2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: less than 8 degrees; 5. No fire, explosion, pollution, chemical corrosion and severe vibration place.

Technical data

Item Unit Parameter
Parameters of voltage, current, life
Rated voltage kV 12
Rated short time power frequency withstand voltage (1min) kV 42
Rated lightning impulse withstand voltage (peak) kV 75
Rated frequency Hz 50
Rated current A 630 1250 630 1250 1250 1600 2000 2500 1600 2000 2500 3150
Rated short-circuit breaking current kA 20 25 31.5 40
Rated short-time withstand current (RMS) kA 20 25 31.5 40
Rated peak withstand current kA 50 63 80 100
Rated short-circuit closing current kA 50 63 80 100
Rated single / back-to-back capacitor bank breaking current A 630/400
Rated short-circuit current duration S 4
Rated short-circuit current breaking times Times 50 30
Rated operating sequence O-t-CO-180s-CO rated short-circuit breaking current less than 31.5kA, t=0.3s rated short-circuit breaking current 40kA, t=180s
Rated operation voltage ≌ 220/110
Mechanical life Times ≥10000
Mechanical property parameters
Open clearance between contacts mm 11±1
Overtravel mm 4±1
Contact closing bounce time ms ≤2 ≤3
Three-phase, switching synchronism ms ≤2
Average opening speed m/s 0.9~1.3
Average closing speed m/s 0.4~0.8
Opening time (rated voltage) ms ≤60
Closing time (rated voltage) ms ≤100

Overall and mounting dimensions(mm)

Type H H1 H2 H3 A A1 A2 B B1 B2 B3
ZN28-12/T 2500 3150 -40 780 700 268 371 581 450 390 700 560 275 690
ZN28-12/T2000-31.5 697 677 235 347 550 380 330 634 480 250 620
ZN28-12/T 630 1250 - 20 31.5 697 677 235 347 550 380 330 594 440 230 580
Rated current 20KA, 25KA, 31.5KA 40kA
Code A B A B
Data 250 610 275 690