Selection
Operating conditions
1. Ambient air temperature: -15℃ ~+40℃ .
2. Altitude: ≤1000m.
3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa.
4. Earthquake intensity: ≤magnitude 8.
5. Applicable in the places without corrosive and flammable gas and water vapor.
6. Used in place without frequently intense vibrant.
Note: Customized products are available.
Features
1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment, andisassembled by bolts or rivets. The structure is fully assembled.
2. The switchgear has various functions to prevent misoperation, including preventing the load-bearing handcart from moving, preventing the live closing and grounding
3. The switchgear is equipped with high-performance VS1 series medium-voltage AC vacuum circuit breakers and solid-sealed vacuum circuit breakers.
4. The busbar adopts heat-shrinkable insulation materials and optimized electrode shapes, with a compact cabinet structure.
This switchgear is technologically advanced, with stable performance, reasonable structure, convenient use, and safe and reliable power distribution equipment
Technical data
No. |
Item |
Unit |
Data |
1 |
Rated voltage |
kV |
3.6, 7.2, 12 |
2 |
Rated frequency of circuit breaker |
Hz |
50 |
3 |
Rated current of circuit breaker |
A |
630, 1250, 1600, 2000, 2500, 3150, 4000 |
4 |
Rated current of switchgear |
A |
630, 1250, 1600, 2000, 2500, 3150, 4000 |
5 |
Rated short-time withstand current (4s) |
kA |
16, 20, 25, 31.5, 40, 50 |
6 |
Rated withstands current (peak) |
kA |
40, 50, 63, 80, 100, 25 |
7 |
Rated short-circuit breaking current |
kA |
16, 20, 25, 31.5, 40, 50 |
8 |
Rated short-circuit closing current (peak) |
kA |
40, 50, 63, 80, 100, 25 |
9 |
Rated
insulation level |
1 min power frequency withstands voltage |
between poles, pole to earth |
kV |
24, 32, 42 |
between open contacts |
kV |
24, 32, 48 |
Lightening impulse
withstands voltage (peak) |
between poles, pole to earth |
kV |
40, 60, 75 |
between open contacts |
kV |
46, 70, 85 |
10 |
Protection level |
|
Shell: IP4X; IP2X when the CPT and CB doors are open |
Note:
1. The short circuit capacity of the current transformer should be separately considered.
2. See technical parameters of ZN63A-12 in related catalogues of our company.
VS1-12 Technical data
Item |
Unit |
Value |
Contact distance |
mm |
12 |
Contact travel |
75 |
Average closing speed (6mm~contact closed) |
m/s |
42 |
Average opening speed (contact separation -6mm) |
20 |
25 |
31.5 |
40 |
Opening time (rated voltage) |
m/s |
630
1250 |
630, 1250, 1600,
2000, 2500, 3150 |
1250, 1600, 2000,
2500, 3150, 4000 |
Closing time (rated voltage) |
Contact closing bounce time |
m/s |
20 |
25 |
31.5 |
40 |
Three phase opening asynchrony |
63 |
80 |
100 |
Allowable cumulative thickness of wear for moving and stationary contacts |
mm |
50 |
63 |
80 |
100 |
Rated short-circuit breaking current breaking times |
Times |
80 |
50 |
30 |
Secondary circuit power frequency withstand current |
V |
2000 |
Rated operating sequence |
|
Opening -0.3s - closing and opening -180s - closing and opening -180s - closing and
opening -180s - closing and opening (40kA |
Rated thermal stability time |
S |
4 |
Rated single/back to back capacitor bank breaking current |
A |
630/400 |
800/400 |
Mechanical life |
Times |
20000 |
10000 |
Structure
Overall and mounting dimensions (refer to picture 2, sheet 2 )
Shape |
Description |
Size(mm) |
Width (W) |
Rated current of branch bus ≤1250A, heat stable current≤40KA |
800(650) |
Rated current of branch bus ≥1600A |
1000 |
Depth (C) |
Cable Incoming and outgoing feeder |
1500 |
Overheaded incoming and outgoing feeder |
1660 |
Height (B) |
|
2300(2200) |
Outline size
Single line diagram
Program No. |
01 |
02 |
03 |
04 |
05 |
06 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets
|
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
2 |
2 |
2 |
3 |
3 |
3 |
Earthing switch JN15 |
/ |
1 |
1 |
/ |
1 |
1 |
Surge arrester HY5W |
/ |
/ |
3 |
/ |
/ |
3 |
Circuit name |
Receiving, feeding |
Receiving, feeding |
Receiving, feeding |
Receiving, feeding |
Receiving, feeding |
Receiving, feeding |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
07 |
08 |
09 |
10 |
11 |
12 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
2 |
2 |
2 |
2 |
3 |
3 |
Earthing switch JN15 |
/ |
1 |
/ |
1 |
/ |
1 |
Circuit name |
Communication
(Right) |
Communication
(Right) |
Communication
(Right) |
Communication
(Right) |
Communication
(Right) |
Communication
(Right) |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
13 |
14 |
15 |
16 |
17 |
18 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets
|
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
3 |
3 |
2 |
2 |
2 |
2 |
Earthing switch JN15 |
/ |
1 |
/ |
1 |
/ |
1 |
Circuit name |
Communication
(Left) |
Communication
(Left) |
Overhead incoming (left communication) |
Overhead incoming (left communication) |
Overhead incoming (right communication) |
Overhead incoming (right communication) |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
19 |
20 |
21 |
22 |
23 |
24 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
3 |
3 |
2 |
2 |
2 |
2 |
Earthing switch JN15 |
/ |
1 |
/ |
1 |
/ |
1 |
Circuit name |
Overhead incoming (left communication) |
Overhead incoming (left communication) |
Overhead incoming (right communication) |
Overhead incoming (right communication) |
Overheaded incoming and outgoing feeder |
Overheaded incoming and outgoing feeder |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
25 |
26 |
27 |
28 |
29 |
30 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1660×2300
1000×1660×2300 |
800×1660×2300
1000×1660×2300 |
800×1660×2300
1000×1660×2300 |
800×1660×2300
1000×1660×2300 |
800×1660×2300
1000×1660×2300 |
800×1660×2300
1000×1660×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
2 |
3 |
3 |
3 |
2 |
2 |
Potential transformer |
/ |
/ |
/ |
/ |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
H.V fuse RN2-10 |
/ |
/ |
/ |
/ |
3 |
3 |
Earthing switch JN15 |
1 |
/ |
1 |
1 |
/ |
1 |
Surge arrester HY5W |
3 |
/ |
/ |
3 |
/ |
/ |
Circuit name |
Overheaded incoming and outgoing feeder |
Overheaded incoming and outgoing feeder |
Overheaded incoming and outgoing feeder |
Overheaded incoming and outgoing feeder |
Cable
incoming+PT |
Cable
incoming+PT |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
31 |
32 |
33 |
34 |
35 |
36 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
CT LZZBJ9 series |
2 |
3 |
3 |
3 |
2 |
2 |
Potential transformer |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
3 |
H.V fuse RN2-10 |
3 |
3 |
3 |
3 |
3 |
3 |
Earthing switch JN15 |
/ |
/ |
1 |
/ |
/ |
/ |
Surge arrester HY5W |
3 |
/ |
/ |
3 |
/ |
/ |
Circuit name |
Cable
incoming+PT |
Cable
incoming+PT |
Cable
incoming+PT |
Cable
incoming+PT |
Cable
incoming+PT |
Cable
incoming+PT |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
37 |
38 |
39 |
40 |
41 |
42 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
1 |
/ |
/ |
/ |
/ |
/ |
CT LZZBJ9 series |
2 |
/ |
/ |
/ |
/ |
/ |
Potential transformer |
JDZ10-10 |
3 |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
2 |
H.V fuse RN2-10 |
3 |
3 |
3 |
3 |
3 |
3 |
Surge arrester HY5W |
3 |
/ |
/ |
3 |
3 |
3 |
|
|
|
|
|
|
|
Circuit name |
Cable
incoming+PT |
Voltage measure |
Voltage measure |
Voltage measure +Surge arrester |
Voltage measure +Surge arrester |
Voltage measure +Surge arrester |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
43 |
44 |
45 |
46 |
47 |
48 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
Potential transformer |
JDZ10-10 |
3 |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
3 |
JDZ10-10 |
2 |
H.V fuse RN2-10 |
3 |
3 |
3 |
3 |
3 |
3 |
Surge arrester HY5W |
3 |
/ |
/ |
/ |
/ |
/ |
|
|
|
|
|
|
|
Circuit name |
Voltage measure +Surge arrester |
Voltage measure +Bus couple |
Voltage measure +Bus couple |
Voltage measure +Bus couple |
Voltage measure +Bus couple |
Voltage measure+Surge arrester+Bus couple |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
49 |
50 |
51 |
52 |
53 |
54 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
Potential transformer |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
3 |
/ |
/ |
/ |
H.V fuse RN2-10 |
3 |
3 |
3 |
/ |
/ |
/ |
Surge arrester HY5W |
3 |
3 |
3 |
/ |
/ |
/ |
Circuit name |
Voltage measure+Surge arrester+Bus couple |
Voltage measure+Surge arrester+Bus couple |
Voltage measure+Surge arrester+Bus couple |
Bus couple |
Bus couple |
Disconnection |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
55 |
56 |
57 |
58 |
59 |
60 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
Potential transformer |
/ |
/ |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
/ |
/ |
H.V fuse RN2-10 |
/ |
/ |
3 |
3 |
/ |
/ |
Earthing switch Jn15 |
/ |
/ |
/ |
/ |
/ |
1 |
Circuit name |
Disconnection+
Communication(Left) |
Disconnection+
Communication(Right) |
Disconnection+
Communication(Left) +Voltage measure |
Disconnection+
Communication(Right)
+Voltage measure |
Outlet and phase exchange |
Outlet and phase exchange |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
61 |
62 |
63 |
64 |
65 |
66 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
CT LZZBJ9 series |
2 |
2 |
3 |
3 |
2 |
2 |
Potential transformer |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
2 |
JDZ10-10 |
3 |
JDZ10-10 |
3 |
H.V fuse RN2-10 |
/ |
/ |
/ |
/ |
/ |
/ |
Circuit name |
Measurement+
left communication |
Measurement+
Right communication
|
Measurement+
left communication |
Measurement+
Right communication
|
Measurement+
left communication |
Measurement+
Right communication
|
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |
Program No. |
67 |
68 |
69 |
70 |
71 |
72 |
Single line diagram |
|
|
|
|
|
|
Overall and mounting dimensions (mm) (Width×Depth×Height) |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
800×1500×2300
1000×1500×2300 |
main elecrical componets |
Rated current(A) |
630~3150 |
VCB(ZN63 or VD4) |
/ |
/ |
1 |
1 |
/ |
/ |
CT LZZBJ9 series |
3 |
3 |
2 |
2 |
2 |
2 |
Potential transformer |
JDZX10-10 |
3 |
JDZX10-10 |
2 |
JDZX10-10 |
2 |
JDZX10-10 |
2 |
JDZX10-10 |
2 |
JDZX10-10 |
2 |
H.V fuse RN2-10 |
3 |
3 |
3 |
3 |
3 |
3 |
Circuit name |
Measurement+
left communication |
Measurement+
Right communication
|
Incoming+ Measurement |
Incoming+ Measurement |
Incoming+ Measurement |
Incoming+ Measurement |
Note |
Cabinet weight will be 1000mm when rated current is above 1600A. |