Operating conditions
1. Ambient temperature:-10~+40℃
2. Altitude: ≤1000m
3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90%
4. Earthquake intensity: ≤8degree
5. Appliable in the place without corrosive, flammable gas and water place
6. With no frequently intense vibrant place around.
Technical data
Item |
Units |
Data |
Rated voltage |
kV |
35 |
Maximum voltage |
kV |
40.5 |
Rated short time withstand current |
kA |
31.5 |
Rated short circuit withstand time |
s |
4 |
Rated short circuit making current |
kA |
80 |
Rated peak withstand current |
kA |
80 |
Rated |
1min power frequency withstand voltage |
kV |
95 |
insulation level |
Lightning Impulse withstand voltage |
kV |
185 |
Central distance between poles |
mm |
300; 350; 400 |
Overall and mounting dimensions(mm)
B |
H |
L |
280 |
750 |
1180 |
300 |
790 |
1180 |
350 |
890 |
1280 |
400 |
990 |
1374 |
Order Notes
1. Indicate product specification, rated voltage, thermal stability current, central distance between poles.
2. If need shaft operating mechanism, indicate right operation mechanism or left operation mechanism according to the operation position shows in the drawing above.
3. If need sensors with electric display device, please indicate the display type.
4. Please consult with our company if you have any special request.
B |
H |
280 |
750 |
300 |
790 |
350 |
890 |
400 |
990 |