Selection
Operating conditions
1. Ambient temperature:-10~+40℃
2. Altitude: ≤1000m (sensor height:140mm)
3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90%
4. Earthquake intensity: ≤8degree
5. Dirtiness degree: II
Technical data
Item |
Units |
Data |
Rated voltage |
kV |
12 |
Rated short time withstand current |
kA |
31.5 |
Rated short circuit withstand time |
s |
4 |
Rated short circuit making current |
kA |
80 |
Rated peak withstand current |
kA |
80 |
Rated |
1min power frequency withstand voltage |
kV |
42 |
insulation level |
Lightning Impulse withstand voltage |
kV |
75 |
Mechanism life |
time |
2000 |
Overall and mounting dimensions(mm)
Copper terminal block
Hole location diagram
Specification |
E |
F |
G |
H |
D |
C |
JN15-12/31.5-165 |
165 |
75 |
160 |
565 |
426 |
|
JN15-12/31.5-180 |
180 |
75 |
160 |
595 |
456 |
|
JN15-12/31.5-200 |
200 |
50 |
160 |
635 |
496 |
|
JN15-12/31.5-210 |
210 |
50 |
185 |
655 |
516 |
|
JN15-12/31.5-220 |
220 |
75 |
185 |
675 |
536 |
|
JN15-12/31.5-230 |
230 |
75 |
185 |
695 |
556 |
96 |
JN15-12/31.5-250 |
250 |
75 |
185 |
735 |
596 |
96 |
JN15-12/31.5-275 |
275 |
75 |
210 |
810 |
646 |
96 |
Order notes:
1. Indicate product specification, central distance between poles, if need the electric display device(type of the display) or not.
2. Need lengthen the soft link or not(normal L=250mm).
3. Please consult with our company if you have any special request.