Home Categories Send inquiry

GW4 Outdoor Isolation Switch

Selection

Technical data

Item Unit Parameters
GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145
Rated voltage KV 40.5 72.5 126 126 145
Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500
Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46)
Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104)
Rated short-time   withstand voltage (effective value) To the ground KV 80 140 185(230) 185 375
Fracture 110 160 210(265) 210 315
Rated lightning impulse withstand voltage (peak) To the ground KV 185 325 450(550) 450 650
Fracture 215 375 520(630) 550 750
Wiring terminal rated the horizontal tension 490(735) 735 735 735 960
Weight of single pole 80 200 240 300 300

Operating conditions

1. Ambient temperature: upper limit +40℃, lower limit -30℃ 2. Altitude: no more than 3000m; 3. Wind speed: no more than 35m/s; 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution level: no more than III class 6. No severe vibration, no corrosive gas, no fire, no explosion danger place.

Overall and mounting dimensions(mm)

1. Wiring terminal 2. Contact 3. Contact finger 4. Support insulator 5. Switch base 6. The main knife operating crank arm 7. The main knife vertical rod (galvanized steel pipe of φ45×45) 8. Anchor ear 9. The main knife operating mechanism (CJ6 or CS17) 10. Grounding contact finger 11. The earth knife vertical rod (galvanized steel pipe of φ45 ×5) 12. The earth knife operating mechanism (CJ78CS17)

GW4 Outdoor Isolation Switch Related Video: