Selection
Operating conditions
1. Altitude: ≤ 2000 meters;
2. Environment temperature: -40℃ ~+85℃;
3. Relative humidity: ≤ 90% (25℃);
4. The maximum daily temperature difference: 25℃;
5. Protection grade: IP67;
6. The maximum ice thickness: 10mm.
Technical data
| Item |
Unit |
Parameter |
| The switch body |
|
|
| Rated voltage |
kV |
12 |
| Power frequency insulation withstand voltage (Interphase and phase to ground / fracture) |
kV |
42/48 |
| Lightning impulse withstand voltage (Interphase and phase to ground / fracture) |
kV |
75/85 (peak) |
| Rated current |
A |
630 |
| Rated short-time withstand current |
kA |
20 |
| Rated thermal stability time |
S |
2 |
| Rated short-circuit close current (peak) |
kA |
40 |
| Rated dynamic stability current (peak) |
kA |
40 |
| Rated cable charging breaking current |
A |
20 |
| Rated switching unloaded transformer inductor current |
A |
<5 |
| Mechanical life |
Times |
10000 |
| Measurement and control unit |
|
|
| Type |
|
FDR-100 |
| Input voltage |
|
AC220±20% |
| Input voltage frequency |
Hz |
50 |
| The output voltage (opening operation) |
|
DC48V |
| Interphase short-circuit protection setting current value |
|
0.2-1.0 adjustable |
| Grounding protection of zero sequence current setting value |
|
10-200mA adjustable |
| Grounding protection action time setting value |
|
0-10s adjustable |
| Setting value permitted error |
|
±5% |
| Insulation resistance (external terminal to ground / input terminal to output terminal) |
|
> 100MΩ/DC500V |
| Power frequency withstand voltage (ibid.) |
|
2000V/1min |
| Impulse withstand voltage (ibid.) |
|
5000V, 1.2/50μs
The positive and negative
three times each |
Overall and mounting dimensions(mm)