Home Categories Send inquiry

FZW28-12F Outdoor Vacuum Load Switch

Selection

Operating conditions

1. Altitude: ≤ 2000 meters; 2. Environment temperature: -40℃ ~+85℃; 3. Relative humidity: ≤ 90% (25℃); 4. The maximum daily temperature difference: 25℃; 5. Protection grade: IP67; 6. The maximum ice thickness: 10mm.

Technical data

Item Unit Parameter
The switch body
Rated voltage kV 12
Power frequency insulation withstand voltage (Interphase and phase to ground / fracture) kV 42/48
Lightning impulse withstand voltage (Interphase and phase to ground / fracture) kV 75/85 (peak)
Rated current A 630
Rated short-time withstand current kA 20
Rated thermal stability time S 2
Rated short-circuit close current (peak) kA 40
Rated dynamic stability current (peak) kA 40
Rated cable charging breaking current A 20
Rated switching unloaded transformer inductor current A <5
Mechanical life Times 10000
Measurement and control unit
Type FDR-100
Input voltage AC220±20%
Input voltage frequency Hz 50
The output voltage (opening operation) DC48V
Interphase short-circuit protection setting current value 0.2-1.0 adjustable
Grounding protection of zero sequence current setting value 10-200mA adjustable
Grounding protection action time setting value 0-10s adjustable
Setting value permitted error ±5%
Insulation resistance (external terminal to    ground / input terminal to output terminal) > 100MΩ/DC500V
Power frequency withstand voltage (ibid.) 2000V/1min
Impulse withstand voltage (ibid.) 5000V, 1.2/50μs The positive and negative three times each

Overall and mounting dimensions(mm)


FZW28-12F Outdoor Vacuum Load Switch Related Video: