Selection
Operating conditions
1. Altitude: no more than 1000m;
2. The environment temperature: upper limit +40℃, lower limit -30℃;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;
4. Saturated steam pressure: daily average value is not higher than 2.2×10 -3 Mpa, monthly average is not higher than 1.8×10 -3 Mpa;
5. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Technical data
Item |
Unit |
Parameter |
Technical parameter of combinations |
Rated voltage |
kV |
12 |
Rated frequency |
Hz |
50 |
The maximum rated current of the fuse |
A |
125 |
Transfer current |
A |
1550 |
The fuse triggered switch segment time |
ms |
40±5 |
Rated short-circuit breaking current |
kA |
31.5 |
Rated short-circuit closing current (prospective peak value) |
kA |
80 |
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) |
kV |
42/49 |
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) |
kV |
75/85 |
Fuse impinger type |
|
Medium-sized |
Technical parameters of vacuum load switch of combined electrical appliance |
Rated voltage |
kV |
12 |
Rated frequency |
Hz |
50 |
Rated current |
A |
630 |
Rated active load breaking current |
A |
630 |
Rated close loop breaking current |
A |
630 |
5% at rated load breaking current |
A |
31.5 |
Rated cable charging breaking current |
A |
10 |
Interrupting no load transformer capacity |
kVA |
1250 |
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) |
kV |
42/48 |
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) |
kV |
75/85 |
4s rated short-time withstand current |
kA |
31.5 |
Rated peak withstand current |
kA |
80 |
Rated short-circuit closing current |
kA |
80 |
Mechanical life |
Times |
10000 |
Allowable cumulative thickness wear in contact |
mm |
2 |
Opening and closing operating torque |
N·m |
≤200 |
Overall and mounting dimensions(mm)
1. Cabinet bracket
2. Disconnector
3. Fuse
4. Insulated tension pole
5. Upper bracket
6. Vacuum interrupter 7. Static contact
8. Insulator
9. Grounding knife
10. Grounding knife spring
11. Opening spring
12. The tripping driving device 13. Insulated tension pole
14. Main axle
15. Layshaft
16. Adjusting yoke
17. Spring operating mechanism