Selection
Operating conditions
1. Ambient temperature: upper limit +40℃, lower limit -30℃;
2. Altitude: ≤2000m;
3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s);
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution grade: III class;
6. Maximum daily temperature variety less than 25℃ .
Technical data
Item |
Unit |
Parameter |
Rated voltage |
kV |
12 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test Wet test |
kV |
42/ fracture 48 |
kV |
34 |
Lightning impulse withstand voltage (peak) |
kV |
75/ fracture 85 |
Rated current |
A |
630, 1250 |
Rated short-circuit breaking current |
kA |
20 |
Rated short-circuit breaking current time |
Times |
30 |
Rated short-circuit closing current (peak) |
kA |
50 |
Rated peak withstand current |
kA |
50 |
Rated short-time withstand current |
kA |
20 |
Rated short circuit duration |
S |
4 |
Opening time |
ms |
<50 |
Closing time |
ms |
<60 |
Full off time |
ms |
≤100 |
Arcing time |
ms |
≤50 |
Mechanical life |
Times |
30000 |
Switch on power |
J |
70 |
Rated operational voltage and auxiliary circuits rated voltage |
V |
DC 220 |
V |
AC 220 |
Overall and mounting dimensions(mm)
Circuit breaker and mounting dimensions
Controller outline and mounting dimensions