ZW32-12 Outdoor Vacuum Circuit Breaker

Selection

Operating conditions

1. The environment temperature: upper limit +40℃, lower limit -30℃ 2. Altitude ≤ 2000 meters 3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s) 4. Earthquake intensity: do not exceed 8 degree 5. Pollution grade: III class 6. Maximum daily temperature: less than 25℃ .

Technical data

Item Unit Parameter
Voltage, current parameters
Rated voltage kV 12
Rated short time power frequency withstand voltage (1min) kV 42/48
Rated lightning impulse withstand voltage (peak) kV 75/85
Rated frequency Hz 50/60
Rated current A 630 1250
Rated short-circuit breaking current kA 20
Rated short-time withstand current (RMS) kA 20
Rated peak withstand current kA 50
Rated short-circuit closing current kA 50
Rated single / back-to-back capacitor bank breaking current A 630/400
Rated short-circuit current duration S 4
Rated short-circuit current breaking times Times 50
The main circuit resistance μΩ ≤80(140)
Rated operational voltage AC/DC≌220
Mechanical life Times 10000
The overcurrent regulating ☆ A 1~10
Quick-break current ☆ A 6~20
The delay time ☆ ms 40~850
Remote control distance ☆ m > 30
Reclose time ☆ Times 0~3
Rated operating sequence ☆ O-0.3s-CO-180s-CO
CT ※ Ratio A ()/5
Capacity VA 15
The output voltage ※ A AC220
The output capacity ※ W 600
The overcurrent regulating ※ A 1~10
The delay time ※ ms 40~850
Remote control distance ※ m 30
Note: the one not marked above is basic technical parameters; marked☆ is intelligent technology parameter; marked ※ is the electronic PT type technical parameters.

Overall and mounting dimensions(mm)

1. operating handle 2. spindle of solation 3. circuit breaker manual on-off handle 4. circuit breaker energy storage handle 5. on-off instructions 6. connection plug 7. current transformer 8. insulator 9. Isolation frame 10. insulated tension pole