Home Categories Send inquiry

ZW20-12 Outdoor Vacuum Circuit Breaker

Selection

Operating conditions

1. Altitude≤2000 meters 2. The environment temperature: -30℃ ~+55℃ outdoor; the highest annual average temperature 20 ℃, the highest daily average temperature 30 ℃; 3. Relative humidity: 95% (25℃) 4. Seismic capacity: horizontal ground acceleration 0.3g, vertical ground acceleration 0.15g, at the same time duration of three sine waves, a safety factor of 1.67 5. Earthquake intensity: 7 degrees 6. The maximum daily temperature difference: 25 ℃ 7. The intensity of sunshine (wind speed 0.5m/s): 0.1W/cm² 8. The maximum wind speed: 34m/s 9. The maximum ice thickness: 10mm 10.Installation position: outdoor, the 10kV overheadline responsibility demarcation point 11.Grounding: neutral non grounding, arc suppression coil grounding and low resistance grounding.

Technical data

Item Unit Parameter
Voltage, current parameters
Rated voltage KV 12
Insulation level of fracture The power frequency (dry and wet test) KV 48
Lightning impulse  test voltage (peak) KV 85
On the ground and interphase insulation level Power frequency Dry test KV 42
Wet test KV 34
Lightning impulse test voltage (peak) KV 75
Rated current A 630
Rated short-circuit breaking current kA 16, 20, 25
Rated short-circuit breaking current interruption times Times 30
Rated short-time withstand current kA 16, 20, 25
Rated short circuit duration S 4
Rated short-circuit close current (peak) kA 40, 50, 63
Rated peak withstand current kA 40, 50, 63
Mechanical life Times > 10000
Rated current on and off times Times 10000
Net weight kg 180
Mechanical properties
Clearance between open contacts mm 9 +1
-0.5
Contact overtravel mm 3 +1
-0.5
Opening speed m/s 1.2±0.2
Closing speed m/s 0.6±0.2
Contact closing jump time ms ≤2
pjase spacing mm 280±2
External charged air insulation distance mm 235±2
External creepage distance cm/kV 3.8
Three phase opening different period ms ≤2
Each phase conductive loop resistance μΩ ≤150
Closing time ms 20~60
Opening time ms 18~45
The energy storage motor rated power W ≯40
The energy storage motor rated voltage V AC220
Rated closing operating voltage V AC220
Maximum / minimum closing operating voltage V AC264/143
Rated opening operation voltage V AC220
Maximum / minimum voltage of motor V AC264/143
Maximum / minimum opening operating voltage V AC242/187
Ratecl pressure SF6 gas (gauge) MPa "0"

Overall and mounting dimensions(mm)