Selection
ZN63 |
- |
24 |
P |
/ |
T |
630 |
- |
25 |
HT |
P210 |
Name |
- |
Rated voltage(KV) |
Pole type |
/ |
Operating mechanism |
Rated current(A)
breaking current(KA) |
- |
Rated short-circuit |
Installation |
Main circuit
wiring direction |
Indoor vacuum circuit breaker |
- |
24:24KV |
No mark:
Insulating
cylinder
type
P: Solid-sealing
type |
/ |
T:
Spring type |
630
1250
1600
2000
2500
3150
4000 |
- |
20
25
31.5
40 |
HT:Handcart type FT:Fixed type |
P210 P275 |
Note:
Zn63 (S) adopts a double spring integral mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the model backup;
Operating conditions
1. Altitude: 1000m and below;
2. Environmental temperature: upper limit+40 ℃, lower limit -25 ℃;
3. Relative humidity: daily average relative humidity not exceeding 95%, monthly average relative humidity not exceeding 90%, saturated vapor pressure: daily average not exceeding 2.2 × 10 MPa, monthly average not greater than 1.8 × 10 Mpa.
4. Seismic intensity not exceeding 8 degrees;
5. A place free from flammable, explosive, or chemically corrosive substances and intense vibrations.
Features
1. The adoption of a new generation modular spring operating mechanism, which features a compact, simple, well-designed structure, reliable transmission, and easy installation.
2. Integration of the operating mechanism and circuit breaker body: it can be used as a fixed installation unit or combined with a dedicated propulsion mechanism to form a handcart unit.
3. The main power circuit primarily utilizes a solid-sealed pole, and an insulation simplification method can also be selected.
4. The main circuit incorporates a solid insulation structure with an integrated solid-sealed pole, achieving maintenance-free, high reliability, and compact size.
5. The circuit breaker is an E2 grade breaker.
6. The cabinet is equipped with comprehensive five-protection interlocking functions.
Technical data
Technical datas are shown in Table 1
Item |
Unit |
Value |
Rated voltage |
kv |
24 |
Rated frequency |
Hz |
50 |
Rated current |
A |
630
1250 |
1250 1600
2000 2500
3150 |
Rated
insulation level |
1min p.f
Wuthstand voltage |
between pole to earth |
kv |
65 |
Separation point |
79 |
Rated lightning
impulse resistance voltage |
between pole to earth |
125 |
Separation point |
145 |
4s rated short time withstand current |
kA |
20 |
25 |
31.5 |
Rated short circuit breaking current |
20 |
25 |
31.5 |
Rated peak thstand current |
50 |
63 |
80 |
Rated short circuit maing curren |
50 |
63 |
80 |
Rated short-circuit duration |
S |
4 |
Rated breaking current at the fsult of different pbasesearthed |
kA |
17.4 |
21.7 |
27.4 |
Rated operation sequence |
|
O-0.3s-CO-18os-CO |
Rated operation voltage |
V |
DC(AC)220/110 |
Electrical endurannce |
|
E2 (grade)* |
Endurannce endurannce |
Time |
20000 |
Note:
1. When the rated current is 3150A, forced air cooling is required
2. The GB1984-2003 electrical life B2 standard is implemented, and the number of short-circuit current interruptions is 274 times.
The mechanical characteristic parameters of the circuit breaker are shown in Table 2
Item |
Unit |
Value |
Opening distance of contact |
mm |
13±1 |
Over-travel distance of contact |
4±1 |
Cental distance between poles |
210,275 |
Permaissibleabrasiom thickness of the comtact |
3 |
Average opening speed (6nm just opening) |
m/s |
1.3±0.3 |
Average closing speed |
0.6±0.2 |
Jumping time after contact closed. |
ms |
≤2 |
Asynchrony of throo phase closing, opening |
≤2 |
Main circuit resistance |
Rated current |
A |
630 |
1250 |
1600 |
2000 |
2500 |
3150 |
Fixed type breaker |
μΩ |
≤50 |
≤45 |
≤35 |
≤35 |
≤30 |
≤25 |
Truck type breaker |
≤55 |
≤50 |
≤50 |
≤40 |
≤35 |
≤30 |
Opening time |
ms |
≤50 |
Closing time |
≤75 |
Operating performances ofoperating mechanise |
85%~110%(rated voltage) |
Reliably close |
85%~110%(rated voltage) |
Reliably open |
≤30%(rated voltage) |
Not open |
Main technical data of operating mechanism as sheet 3
Item |
Unit |
Value |
Rated opcrating voltage for opening |
V |
AC/DC220V、AC/DC11oV |
Rated operating voltage for closing |
AC/DC220V、AC/DC110V |
Rated instantaneous over-current tripping curent |
A |
5/3.5 |
Rated voltage for charging mnotor |
V |
AC/DC220V、AC/DC11oV |
Rated output power of charging motor |
W |
70 |
Charging time |
S |
≤10 |
1min p.f withstland voltage on secondary circnit |
V |
2000 |
Overall and mounting dimensions(mm)
ZN63(VS1)-24 hand car phase distance 210 outline dimensions (small solid sealed pole type)
Rated current (A) |
Rated short-circuit breaking current (kA) |
Equipped static contact size (mm) |
630 |
25 |
Φ35 |
1250 |
25 |
Φ49 |
ZN63(VS1)-24 hand car phase distance 275 outline dimensions (small solid sealed pole type)
Rated current (A) |
Rated short-circuit breaking current (kA) |
Equipped static contact size (mm) |
630 |
25 |
Φ35 |
1250 |
25 |
Φ49 |
1600 |
31.5 |
Φ45 |
ZN63(VS1)-24 hand car phase distance 275 outline dimensions (big solid sealed pole type)
Rated current (A) |
Rated short-circuit breaking current (kA) |
Equipped static contact size (mm) |
1600-2000 |
31.5 |
Φ79 |
2500-3150 |
31.5 |
Φ109 |