Home Categories Send inquiry

KYN61-40.5 Metalclad AC Enclosed Switchgear, Withdrawable Type

Selection

Operating conditions

1. Ambient air temperature: -15℃ ~+40℃ 2. Altitude: ≤1000m 3. Relative humidity : Daily average≤95%; Monthly average≤90% 4. Earthquake intensity:≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available.

Features

1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment and assembled with bolts or rivets, with a fully modular structure. 2. This switchgear has various functions to prevent misoperations, including preventing loaded trolleys from moving, preventing live coupling and earthing switches, and preventing inadvertent entry into live compartments. 3. The switchgear is equipped with a ZN85 vacuum circuit breaker with excellent performance and a handcart, and the main busbar is connected without the need for transitional transfer. 4. This switchgear is an advanced, stable performance, reasonable structure, easy-to- use, safe and reliable power distribution equipment

Technical data

Switchgear parameter
No. Item Unit Value
1 Rated voltage kV 40.5
2 Rated current A 630/1250/1600/2000/2500
3 Rated frequency Hz 50/60
4 Power frequency withstand voltage in 1 min Phase,Earthed kV 95
lsolating Fracture kV 110
5 Lightning impulse withstand voltage(Peak) Phase,Earthed kV 185
lsolating Fracture kV 215
6 Rated current of the main busbar A 630/1250/1600/2000/2500
7 Rated current of the branch busbar A 630/1250/1600/2000/2500
8 Rated short-circuit breaking current kA 20/25/31.5
9 Rated short-time withstand current kA 20/25/31.5
10 Rated peak withstand current kA 50/63/80
11 Rated short circuit making current kA 50/63/80
12 Frequency withstand voltage in 1min of aux control loop V 2000
13 lnternal arc duration test(0.5s) kA 31.5
14 Degress of protection IP IP4X(IP2X when the front door is opened)
15 Rated voltage of aux control loop V AC or DC 110/220
ZN85-40.5 parameter
No. Item Unit Data
1 Rated voltage kV 40.5
2 Rated insulation level lightning impulse withstand voltage (full wave) kV 185
1 min power frequency withstand voltage kV 95
3 Rated frequency Hz 50
4 Rated current kA 630 630,1250 1250,1600,2000,2500
5 Rated short -circuit breaking current kA 20 25 31.5
6 Rated short -circuit making current kA 50 63 80
7 Rated withstands current (peak) kA 50 63 80
8 Rated short-time withstand current kA 20 25 31.5
9 Fixed breaking time s ≤0.07
10 Making time Electro-magnetic mechanism s Electro-magnetic mechanism ≤0.2
Spring mechanism s Spring mechanism ≤0.10
11 Rated operation sequence / Open-0.3s-close open-180s-close open
12 Mechanical life times 10000

Features

Single line diagram

 
Program No. 01 02 03 04
Single line diagram
VCB ZN85-40.5 1 1 1 1
Main electrical components JNH1-40.5 0-1 0-1 0-1 0-1
CT  LZZB7,8,9-40.5 / 1 2 3
Application Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder
Note
 
Program No. 05 06 07 08
Single line diagram    
Main electrical components   VCB ZN85-40.5 1 1 1 1
JNH1-40.5 0-1 0-1 0-1 0-1
CT  LZZB7,8,9-40.5 / 1 2 3
Application Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder
Note
 
Program No. 09 10 11 12
Single line diagram
Main electrical components VCB ZN85-40.5 1 1 1 1
CT  LZZB7,8,9-40.5 / 1 2 3
Application Left(right)communicating Left(right)communicating Left(right)communicating Left(right)communicating
Note
 
Program No. 13 14 15 16
Single line diagram
Main electrical components CT  LZZB7, 8, 9-40.5 / 1 2 3
Application Left(right)communicating Left(right)communicating Left(right)communicating Left(right)communicating
Note
 
Program No. 17 18 19 20
Single line diagram      
Main electrical components VCB LZZB7,8,9-40.5 / 1 2 3
JNH1-40.5 0-1 0-1 0-1 0-1
Application Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder
Note
 
Program No. 21 22 23 24
Single line diagram        
Main electrical components VCB LZZB7,8,9-40.5 / 1 2 3
JNH1-40.5 0-1 0-1 0-1 0-1
Application Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder Overhead incoming  and outgoing feeder
Note
 
Program No. 25 26 27
Single line diagram      
CT LZX9-40.5Q 2 3 /
Main electrical components Fuse XPNP-40.5 3 3 3
Arrester HY5W-51 / / 3
Application Potential   transformer Potential   transformer Potential   transformer
Note

KYN61-40.5 Metalclad AC Enclosed Switchgear, Withdrawable Type Related Video: