Selection
Operating conditions
1. Ambient temperature:-10~+40℃
2. Altitude: ≤1000m (sensor height:140mm)
3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90%
4. Earthquake intensity: ≤8degree
5. Dirtiness degree: II
Technical data
Item |
Units |
Data |
Rated voltage |
kV |
12 |
Rated short time withstand current |
kA |
40 |
Rated short circuit withstand time |
s |
4 |
Rated short circuit making current |
kA |
100 |
Rated peak withstand current |
kA |
100 |
Rated |
1min power frequency withstand voltage |
kV |
42 |
insulation level |
Lightning Impulse withstand voltage |
kV |
75 |
Mechanism life |
time |
2000 |
Overall and mounting dimensions(mm)
Copper terminal block
Hole location diagram
Specification |
E |
F |
G |
H |
D |
JN17-12/40-210 |
210 |
50 |
185 |
655 |
516 |
JN17-12/40-220 |
220 |
50 |
185 |
675 |
536 |
JN17-12/40-230 |
230 |
50 |
185 |
695 |
556 |
JN17-12/40-250 |
250 |
50 |
185 |
735 |
596 |
JN17-12/40-275 |
275 |
50 |
210 |
810 |
646 |
Order notes:
1. Indicate product specification, central distance between poles, whether need the electric display device(type of the display) or not.
2. Need lengthen the soft link or not(normal L=250mm)
3. Please consult with our company if you have any special request.