HXGN15 Air-insulated RMU(Fixed Type)

Selection

Operating conditions

1. Ambient air temperature: -15℃ ~+40℃ . Daily average temperature:≤35℃ . 2. Altitude: ≤1000m. 3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa Monthly average≤90%, monthly averange of vapour pressure≤1.8kpa. 4. Earthquake intensity: ≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available.

Technical data

No. Item Unit Data
1 Rated voltage kV 12
2 Rated current Load break switchgear A 630
Combined switchgear A 125
3 Rated short-circuit breaking current kA 31.5
4 Rated active on-load breaking current A 630
5 Rated short-time withstands current kA 20
6 Rated withstands current(Peak) kA 50
7 Rated power frequency voltage withstands    inter-phase,to earth and to the open contact kV 42/48
8 Thundering withstands voltage inter-phase, to earth and to the open contact kV 75/85
9 Mechanical life times 10000
10 Rated take-over curent A 3150
11 Operating mode / Manual or automatic
12 Protection level / IP2X

Loop power supply principle

The loop power supply is composed of three basic unit to separate any one of the failure line and ensure the continuous power supply through the other unit. The branch line for the user could separated and protect the transformer which could facilitate the maintenance. The loop power supply could be expanded as per the user's requirements to form various protection plans.

Feature

1. 8MF material adopted for the switchgear,modular holes available with E=200. 2. Switch disconnector ,vacuum load breaker switch, earthing switch and the switchgear door reliably interlocked,which could avoid miss operation. 3. Both manual and automatic operation are available. 4. There isleas sealed pin at the door of measurement chamber and meter chamber. 5. Prompt tripping could be realized to protect the equipments. 6. The design facilitate the operation at the front panel and the switchgear could be installed alongside the wall. 7. The switchgear is featured for its complete interlocking function: the load break switch could be operated to the making status when the switchgear door is closed and locked and the earthing switch to the making position. When the earthing switch is at making status, input the insulation clapboard to its position, the switchgear door then, could be operated. 8. The Vacuum arc-extinguishing chamber and fuse are reliably connected. So as the fuse & switchgear door and insulation clapboard & the switchgear door.

Overall and mounting dimensions(mm)

Main single line diagram

Program No. 01 02 03 04 05 06
Single line diagram            
Application Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder
Isolation/Load/Combined apparatus GN □-12D GN □-12D GN □-12D GN □-12D GN □-12D GN □-12D
Fuse / RN3 / / / /
Current transformer / / / / LZZBJ9 LZZBJ9
Surge arrester / HY5W / / / /
 
Program No. 07 08 09 10 11 12
Single line diagram
Application Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder Cable incoming and outgoing feeder
Isolation/Load/Combined apparatus FZN21-12D FZN21-12D FZN21-12D FZN21-12D FZN21-12D FZN21
Fuse / / / RN2 RN2 RN2
Current transformer / LZZBJ9 LZZBJ9 / LZZBJ9 LZZBJ9
Potential transformer / / / JDZ JDZ JDZ
Surge arrester HY5W HY5W HY5W / / /
 
Program No. 13 14 15 16 17 18
Single line diagram            
Application Metering cable incoming Metering cable incoming Cable incoming and outgoing feeder Cable incoming and outgoing feeder Metering cable incoming Overheaded incoming cable outgoing
Isolation/Load/Combined apparatus FZN21-12D FZN21-12D FZN21-12D FZN21-12D / GN □-12D
Fuse RN2 S □ LAJ S □ LAJ S □ LAJ RN2 RN3
Current transformer LZZBJ9 / LZZBJ9 LZZBJ9 LZZBJ9 /
 
Program No. 19 20 21 22 23 24
Single line diagram            
Application Overheaded incoming cable outgoing Overheaded incoming cable outgoing Overheaded incoming cable outgoing Overheaded incoming cable outgoing Overheaded incoming cable outgoing Overheaded incoming cable outgoing
Isolation/Load/Combined apparatus FZN21-12D FZN21-12D FZN21-12D FZN21-12D FZN21-12D FZN21-12D
Fuse / / / S □ LAJ S □ LAJ S □ LAJ
Current transformer / LZZBJ9 LZZBJ9 / LZZBJ9 LZZBJ9
 
Program No. 25 26 27 28 29 30
Single line diagram            
Application Communication Communication Measure and   Communication Measure and   Communication OverheadedincomingCommunication OverheadedincomingCommunication
Isolation/Load/Combined apparatus FZN21-12D FZN21-12D / / FZN21-12D FZN21-12D
Fuse / S □ LAJ RN2 RN2 / S □ LAJ
Current transformer / / LZZBJ9 LZZBJ9 / LZZBJ9
Potential transformer / / JDZ JDZ / /
 
Program No. 31 32 33 34 35 36
Single line diagram            
Application OverheadedincomingCommunication Measurement Potential   transformer Potential   transformer Potential   transformer Potential   transformer
Isolation/Load/Combined apparatus / / GN □-12 GN □-12 GN □-12 GN □-12
Fuse RN2 RN2 RN2 RN2 RN2 RN2
Current transformer LZZBJ9 LZZBJ9 / / / /
Potential transformer JDZ JDZ JDZ JDZJ JDZJ JDZJ
Surge arrester / / / / HY5W HY5W
 
Program No. 01 02 03 04 05 06 07 08
Single line diagram
Application Cableincoming Left (right)    communication PTcableincoming PT left (right) communication Overheadedincomingcable incoming Overheadedincomingleft (right) communication Cableoutgoing Cableoutgoing
Overall and mounting dimensions (mm) (Width×Depth×Height) 375×960×1600 375×960×1600 500×960×1600 500×960×1600 375×960×1600 375×960×1600 375×960×1600 500×960×1600
main elecrical componets Type QTY.
FLN36-12D/630-20 1 1 1 1 1 1 / /
FLN36-12D/125-31.5 / / / / / / 1 1
RN2-0.05A / / 3 3 / / / /
SDLDJ/SFLDJ/SKLDJ / / / / / / 3 3
LZZS-10Q   LZZB9-10C LZZB-10 2 or 3 2 or 3 / / 2 or 3 2 or 3 / 1 / 2 / 3
JDZX10-10A JDZ8-10 / / 2 or 3 2 or 3 / / / /
HY5WZI-17/45 / (3) / / / / / /
DZN4-T1.2 1 1 1 1 1 1 1 1
 
Program No. 09 10 11 12 13 14 15 16
Single line diagram
Application Meteringcableincoming Meteringcableincoming Measurement Measurement Cableincoming Buselevated Overheadincomingcable outgoing Overheadincomingcable outgoing
Overall and mounting dimensions (mm) (Width×Depth×Height) 500×960×1600 500×960×1600 375×960×1600 375×960×1600 375×960×1600 375×960×1600 375×960×1600 500×960×1600
main elecrical componets Type QTY.
FLN36-12D/630-20 / / / / / / / /
FLN36-12D/125-31.5 / / / / / / 1 1
RN2-0.05A 3 3 3 3 / / / /
SDLDJ/SFLDJ/SKLDJ / / / / / / 3 3
LZZS-10Q LZZB9-10C LZZB-10 2 or 3 2 or 3 2 or 3 2 or 3 / / / 1 / 2 / 3
JDZX10-10A JDZ8-10 2 or 3 2 or 3 2 or 3 2 or 3 / / / /
HY5WZI-17/45 3 / / / (3) / / /
DZN4-T1.2 1 / / / 1 / 1 1