Selection
Operating conditions
1. The ambient temperature: upper limit +40℃,lower limit -40 ℃;
2. Altitude: no more than 3000m;
3. Wind speed: not more than 35m/s;
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution level: no more than III;
6. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Technical data
Item |
|
Parameters |
Unit |
GW5- 40.5 |
GW5-72.5 |
GW5-126 |
GW5-145 |
Rated voltage |
kV |
40.5 |
72.5 |
126 |
145 |
Rated current |
A |
630/1250/1600/2000 |
Rated frequency |
Hz |
50 |
Disconnector |
Rated peak withstand current |
kA |
50/80/100 |
Rated short-time withstand current |
kA |
20/31.5/40 |
Rated short circuit duration |
s |
4 |
I type
earth knife |
Rated peak
withstand current |
kA |
25 |
Rated short-time withstand current |
kA |
10 |
Rated short
circuit duration |
s |
4 |
II type
earth knife |
Rated peak
withstand current |
kA |
100 |
Rated short-time withstand current |
kA |
40 |
Rated short
circuit duration |
s |
2 |
Overall and mounting dimensions(mm)
1. Connecting terminal
2. Main contact
3. Main contact finger
4. Porcelain insulator
5. Switch base
6. Cross-pin type joint
7. The main knife vertical rod
(1 galvanized steel user owned)
8. Friction plate
9. The main operating mechanism
(CJ6 electric operation or CS17 manual operation)
10. The main knife three-phase linkage rod
The main knife handle at the closing position
The main knife handle is in the off position
Earthing switch operation handle is in the closing position
Earthing switch operation handle is in the off position