Selection
Operating conditions
1. The altitude above sea level: 2000m
2. The ambient air temperature: -40℃~40℃ wind speed does not exceed 35m/s.
3. The earthquake intensity does not exceed 8 degrees.
4. The working situation is without frequent violent vibration.
5. The installation site of ordinary type isolator s hould be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction
capability of the isolator .
6. Pollution i-proof type isolator is applicable to severe filthy conduction area, however, it shouldn't be any explosive matters and matters causing fire .
Technical data
| Item |
Unit |
Technical parameters |
| Rated voltage |
kV |
10 |
15 |
20 |
| Max. operating voltage |
kV |
12 |
17.5 |
24 |
| Rated insulation level |
1min. power frequency withstand voltage |
To earth |
kV |
38 |
42 |
50 |
| Across open DS |
kV |
42 |
48 |
60 |
| Rated lightning impulse withstand voltage |
To earth |
kV |
75 |
105 |
125 |
| Across open DS |
kV |
85 |
120 |
145 |
| Rated frequency |
Hz |
50 |
| Rated current |
A |
200 |
400 |
630 |
1250 |
| 4s short time withstand current |
kA |
6.3 |
12.5 |
20 |
31.5 |
| Peak withstand current |
kA |
16 |
31.5 |
50 |
80 |
| Mechanism supplied for disconnector |
|
CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism |
| Item |
Unit |
Technical parameters |
| Rated voltage |
kV |
12 |
24 |
33 |
| Max. operating voltage |
kV |
15 |
27 |
35 |
| Rated insulation level |
1min. power frequency withstand voltage |
To earth |
kV |
40 |
50 |
80 |
| Across open DS |
kV |
47 |
60 |
90 |
| Rated lightning impulse withstand voltage |
To earth |
kV |
105 |
125 |
180 |
| Across open DS |
kV |
120 |
145 |
210 |
| Rated frequency |
Hz |
50 |
| Rated current |
A |
200 |
400 |
630 |
1250 |
| 4s short time withstand current |
kA |
6.3 |
12.5 |
20 |
31.5 |
| Peak withstand current |
kA |
16 |
31.5 |
50 |
80 |
| Mechanism supplied for disconnector |
|
CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism |
Overall and mounting dimensions(mm)
Connect pole
1. Φ12Spindle
2. Washer12
3. Open bolt4 25
4. Bend coupling
5. M16Nut
6. Pole
7. 3/4" Water gas pipe
8. Connect pole head
| Product model number |
A |
B |
C |
| GW1-12G/400A |
510 |
555 |
18 ×24 =4 |
| GW1-12G/630A |
530 |
555 |
18 ×24 =4 |
| GW1-24G/400A |
510 |
555 |
18 ×24 =4 |
| GW1-24G/630A |
530 |
555 |
18 ×24 =4 |