Selection
Operating conditions
1. The altitude does not exceed 1000m;
2. Ambient air temperature: -10 ℃ ~+40 ℃;
3. Relative humidity: daily average value is not greater than 95%, monthly average value is not greater than 90%;
4. Contamination grades: no serious dust, corrosive and explosive material place;
5. Earthquake intensity: do not exceed 8 degree; No regular violent vibration place.
Technical data
Product specifications
Parameter |
GN30-12/
400-12.5 |
GN30-12/
630-12.5 |
GN30-12/
1000-12.5 |
GN30-12/
1250-12.5 |
GN30-12/
1600-12.5 |
Item |
GN30-12D/
400-12.5 |
GN30-12D/
630-12.5 |
GN30-12D/
1000-12.5 |
GN30-12D/
1250-12.5 |
GN30-12D/
1600-12.5 |
Voltage, current parameters |
Rated voltage (kV) |
|
|
12 |
|
|
Rated current (A) |
400 |
630 |
1000 |
1250 |
1600~3150 |
Rated short-time |
12.5 |
20 |
31.5 |
31.5 |
40 |
withstand current (kA) |
Rated short-time duration (S) |
4 |
4 |
4 |
4 |
4 |
Rated peak withstand current (KA) |
31.5 |
50 |
80 |
80 |
100 |
Rated
insulation level |
1 min power frequency
withstand
voltage (KV) |
Between pole, pole to earth 42 fracture 48 |
Lightning
impulse
voltage (kV) |
Between pole, pole to earth 75 fracture 85 |
Overall and mounting dimensions(mm)
1. Vertical incoming contact
2. Vertical contact support
3. Rotating moving contact
4. Insulator
5. Grounding contact
6. Parallel contact support
7. Parallel outgoing contact
8. Rack
9. Name plate
10.Opening and closing crank arm
Notes
Outline and installation dimensions of isolation switches on a distance of 210mm The incoming and outgoing line methods are: parallel incoming line and parallel outgoing line: