Home Categories Send inquiry

GCS Low-voltage Switchgear Panel, Withdrawable Type

Selection

Operating conditions

1. Ambient air temperature: -15℃ ~+40℃ Daily average temperature: ≤35℃ When the actual temperature exceed the range, it should be used by reducing the capacity accordingly. 2. Altitude: ≤2000m 3. Relative humidity: ≤50%, when temperature is +40℃ When temperature is low, larger relative humidity is allowed. when it is +20℃, relative humidity can be 90%. Since the temperature change will make out condensation. 4. Installation inclination: ≤5% 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available.

Technical data

Item Data
The main circuit of rated voltage(V) AC400, 690
The auxiliary circuit of rated voltage(V) AC220, 400; DC110, 220
Rated frequency(Hz) 50(60)
Rated insulation voltage(V) 660(1000)
Rated current(A) Horizontal busbar ≤4000
Vertical bus(MCC) 1000
Busbar rated short time withstand current(KA/1S) 50, 80
Busbar rated peak withstand current(KA/0.1s) 105, 176
Power frequency test voltage (V/1Min) Main circuit 2500
Auxiliary circuit 2000
Main Busbar 3 Phase 4 Wires A, B, C, N
3 Phase 5 Wires A, B, C, PE, N

Features

1. C type material adopted for the mainframe, frame use the form of Assembling structure. Main frame have the installation modular hole E=20mm 2. The Compartment is divided into functional unit rooms, bus room, cable rooms,Each unit is relatively independent .” 3. Take the drawer as main body, meanwhile have the draw out type and fixed type, can mixed combination, Arbitrary selection. 4. Cabinet size (refer to sheet 2)
Height 2200
Width 400 600 800 1000
Depth 600 800 1000
5. Functional unit 1) The higher modulus of drawer is 160mm, divide to1/2 unit, 1 unit, 1.5unit, 2 unit,3 unit 5 different size series. Unit loop rated voltage below 400A. 2) The same functional unit of the drawer has good interchangeability.Each MCC cabinet can install max 11 set drawer with 1 unit, or 3) 22 sets drawer with 1/2 unit. Drawer with more than 1 unit adopt multi-functional plate. 4) Drawer incoming and outgoing line adopt the same standardized plug of slice structure with different quantity according to current 5) The transfer between ½ unit drawer and cable cabinet use ZJ-2 adapter.. 6) The transfer between drawer which is above 1 unit and cable cabinet use standardized bar type or tube type ZJ-1 adapter according to different current rated. 7) Drawer panel have the open, close, test, draw out position indicator. 8) Drawer unit have Mechanical linkage. 9) Feeder cabinet and motor control cabinet have special cable insulation cabinet. The connection between functional unit and cable cabinet adopt adapter. Not only improves the reliability of the cable, and greatly facilitates the user safety and repair of cable. 6. Busbar In order to improve the bus dynamic thermal stability and improved contact surface temperature rise, device use TMY-T2 series of hard copper, Copper plate surface will be treated with new advanced oxidation process. The performance index is superior to the traditional tin plating process. 1) Horizontal busbar Horizontal busbar is arranged in Busbar compartment at the back of cabinet,double busbar for above 2500 A, single layer busbar for current below 2500A.Each phase is composed of 4 or 2 pcs busbar ,improve the Short circuit strength of bus. 2) Vertical bus "L" shape hard copper tin bus is used for vertical busbar of drawer.L type bus specification(mm): (Height ×thickness)+(button×Thickness)(50 ×5)+(30 ×5)Rated current 1000A Neutral grounding busbar 3) Adopt hard copper. Through the level of neutral grounding wire (PEN) or ground +neutral line (PE+N).

Overall and mounting dimensions(mm)

Electric power, communication cabinet installation diagram
Cabinet code A B C D Remark
GCS-TG1010-4 1000 1000 900 900 Communication cabinet
GCS-TG0810-4 800 1000 700 900 Electric power cabinet
GCS-TG0808-4 800 800 700 700 Electric power cabinet
GCS-TG0608-4 600 800 500 700 Electric power cabinet
PC cabinet installation diagram
Cabinet code A B C D E F ×G
GCS-TG1010-2 1000 1000 900 900 60 400×400
GCS-TG0810-2 800 1000 700 900 160 200×400
GCS-TG1008-2 1000 800 900 700 60 400×400
GCS-TG0808-2 800 800 700 700 160 200×400
MCC cabinet installation diagram
Cabinet code A B C D E F ×G
GCS-TG1008-1 1000 800 900 700 60 400×350
GCS-TG1006-1 1000 600 900 500 60 400×350
GCS-TG0806-1 800 600 700 500 160 200×350

Main single line diagram

Program No. 01 02 03 04
Single line diagram  
Application Electric power (up incoming) Electric power(bottom incoming) Electric power(Electric cable incoming) Communication
Specification No. A B C D E F G  A  B  C  D  E  F  G  A  B  C  D  E  A  B  C  D  E  F  G

Short time withstand   current/Instantaneous withstand current(kA)

80/176  80/176
50/105  50/105  50/105  50/105
30/63  30/63  30/63  30/63

Main electric components

Rated current(A)

4000

3150

2500

2000

1600

1000

630  4000  3150  2500  2000  1600  1000  630  2500  2000  1600  1000  630  4000  3150  2500  2000  1600  1000  630
YCW1-4000 1  1 1
YCW1-3200 1  1 1
YCW1-3200 1  1 1 1
YCW1-2000 1  1 1 1
YCW1-2000 1 1 1
YCW1-2000 1  1 1 1
YCW1-2000 1  1 1 1
SDL-□   (1)   (1)   (1)   (1)   (1)
SDH-□□/5 3(4) 3(4) 3(4) 3(4) 3(4) 3(4) 3(4)  3(4)  3(4)  3(4)  3(4)  3(4)  3(4)  3(4)  3  3  3  3  3  3  3
Cabinet width(mm) 800(1000) 600  800(1000)  600   800   600  1000    800
Cabinet depth(mm) 1000 800  1000  800   800  1000    800
Small compartment height usage(mm)
 
Program No. 05 06 07 08
Single line diagram
Application Bus switching Feeder Dual power switch manually Dual power switch manually

Main electric components

     
Specification No. A B A B A B
80/176 50/105
current/Instantaneous 50/105 50/105 30/63
Rated current(A)  4000  3150 2500  2500  2000 1000 630
YCW1-2000  1
YCW1-2000  1 1
YCW1-2000 1 1
QPS-1000 1 1
QPS-630 1
SDL-□  (1)   (1)   (1)
SDH-□□/5 1(3) 3(4) 3(4)
Cabinet width(mm) 400(600) 1000 1000
Cabinet depth(mm) 400(600) 800(1000) 800
Small compartment height usage(mm) 640
 
Program No. 09 10 11 12
Single line diagram
Application Dual power supply switching Feeder Feeder Current-limiting reactor
Specification No. A B A B C D
50/105 50/105 50/105
current/Instantaneous withstand current(kA) 30/63 30/63 30/63
 Main electric components Rated current(A) 400 250 630 400 250 160 400 250 100 600
QSA-630 1
QSA-400 1
QSA-250 1
QSA-160 1
Current-limiting reactor600A0.0084Ω/Φ 3
B370, LR1, CJ35 1
B250, LR1, CJ35 1
TG-400BD, YCM1-400L, TM30 1 1 1
TG-225BD, YCM1-225M, TM30 1
TG-100BD, YCM1-100M, TM30 1
SDL-□ (1) (1) 1
SDH-□□/5
Cabinet width(mm) 800(1000) 1000 800(1000) 800
Cabinet depth(mm) 600(800) 800(1000) 600(800) 600
Small compartment height usage(mm) 480 ×2 480 320 240(160)
 
Program No. 13 14 15
Single line diagram      
Application Potential transformer Potential transformer Potential transformer
Main electric components Specification No.
Rated current(A)
QSA-63  1  1
NT00-□  3
JDG-0.5 380/100  2  2  1
JSGW-0.5
SDH-□□/5
Cabinet width(mm) Install in the electric power cabinet or 05 scheme Switching cabinet, connect with branch bus,Not occupy the space.
Cabinet depth(mm)
Small compartant height(mm)
 
Program No. 16 17 18
Single line diagram
Application  Static Var Compensator Static Var Compensator  Public power
 Specification No.  A  B  C  A  B  C
Max control motor power (kW)  160  128  96  160  128  96
Main electric components  QA-400 1  1  1  1  1  1
 am-32  30  24  18  30  24  18
 NT00-  3
 JBK3-400  1
 B30C  10  8  6  10  8  6
 T45, LR1  10  8  6  10  8  6
 BCMJ-0.4-16-3  10  8  6  10  8  6
 SDH-OO/5  3  3  3  3  3  3
Cabinet width(mm)  1000  800  1000  800
Cabinet depth(mm) 800(600) 800(600)
Small compartment height usage(mm)
 
Program No. 19 20 21 22
Single line diagram
Motor (reversible) Motor (reversible) Motor (irreversible) Motor (irreversible)
Specification No. A B 7.5 A B C A B
Max control motor power (kW) 37 15 100 75 75 37 15 7.5
   

Main elecric componets

           
QSA-125 1
HH17-63 1 3
NT00-□
YCM1-400L or TG-400BD, TM30 1
YCM1-225M, TM30, TG225BD 1 1
YCM1-1000L or TG-100BD, TM30 1 1
NZMS4, TM30 1
B250, LC1, CJ35 1
B170-105, LC1, CJ35 1 1
B85 or LC1-D80 2 1
B45 or LC1-D32 2 1
B16 or LC1-D18 2 1
T85, LR1 1 1
TSA45, LC1 1 1
T16, LR1 1 1 1 1 1
SDL-□ (1) (1) (1) (1) (1) (1) (1) (1) (1)
SDH-□□/5 1 1 1 3 3 3 1 1 1
Small compartment height usage(mm) 320 160 160 480 320 320 160
Program No. 23 24 25 26
Single line diagram
Application Y-Δ Start Y-Δ Start Y-Δ Start Y-Δ Start
Specification No. A B A B A B A B
Max control motor power (kW) 160 90 37 15 160 90 37 15
 

Main elecric componets

         
QSA-400~250 1 1
QSA-125 1
HH17-63 1
NT3-□ 3
TG-400B 1
YCM1-225 or TG-225D 1
YCM1-100M or TG-100D 1 1
B370+B250 2+1 2+1
B250+B170 2+1 2+1
B85 or LC1-D80 3 3
B45, TC1-D32 or 3TB44 3 3
T85 1 1
TSA45 1 1
T16 1 1 1 1
SDL-□ (1) (1) (1) (1) (1) (1) (1) (1)
SDH-□□/5 3 3 1 1 1 1 1 1
Cabinet width(mm)
Cabinet depth(mm)
Small compartment height usage(mm) 1120 960 320 800 320