Selection
Operating conditions
1. Ambient air temperature: -15℃ ~+40℃
Daily average temperature: ≤35℃
When the actual temperature exceed the range, it should be used by reducing the capacity accordingly.
2. Altitude: ≤2000m
3. Relative humidity: ≤50%, when temperature is +40℃
When temperature is low, larger relative humidity is allowed. when it is +20℃, relative humidity can be 90%. Since the temperature change will make out condensation.
4. Installation inclination: ≤5%
5. Applicable in the places without corrosive and flammable gas.
Note: Customized products are available.
Technical data
Item |
Data |
The main circuit of rated voltage(V) |
AC400, 690 |
The auxiliary circuit of rated voltage(V) |
AC220, 400; DC110, 220 |
Rated frequency(Hz) |
50(60) |
Rated insulation voltage(V) |
660(1000) |
Rated current(A) |
Horizontal busbar |
≤4000 |
Vertical bus(MCC) |
1000 |
Busbar rated short time withstand current(KA/1S) |
50, 80 |
Busbar rated peak withstand current(KA/0.1s) |
105, 176 |
Power frequency test voltage (V/1Min) |
Main circuit |
2500 |
Auxiliary circuit |
2000 |
Main Busbar |
3 Phase 4 Wires |
A, B, C, N |
3 Phase 5 Wires |
A, B, C, PE, N |
Features
1. C type material adopted for the mainframe, frame use the form of Assembling structure. Main frame have the installation modular hole E=20mm
2. The Compartment is divided into functional unit rooms, bus room, cable rooms,Each unit is relatively independent .”
3. Take the drawer as main body, meanwhile have the draw out type and fixed type, can mixed combination, Arbitrary selection.
4. Cabinet size (refer to sheet 2)
Height |
2200 |
|
|
|
Width |
400 |
600 |
800 |
1000 |
Depth |
600 |
800 |
1000 |
|
5. Functional unit
1) The higher modulus of drawer is 160mm, divide to1/2 unit, 1 unit, 1.5unit, 2 unit,3 unit 5 different size series. Unit loop rated voltage below 400A.
2) The same functional unit of the drawer has good interchangeability.Each MCC cabinet can install max 11 set drawer with 1 unit, or
3) 22 sets drawer with 1/2 unit. Drawer with more than 1 unit adopt multi-functional plate.
4) Drawer incoming and outgoing line adopt the same standardized plug of slice structure with different quantity according to current
5) The transfer between ½ unit drawer and cable cabinet use ZJ-2 adapter..
6) The transfer between drawer which is above 1 unit and cable cabinet use standardized bar type or tube type ZJ-1 adapter according to different current rated.
7) Drawer panel have the open, close, test, draw out position indicator.
8) Drawer unit have Mechanical linkage.
9) Feeder cabinet and motor control cabinet have special cable insulation cabinet. The connection between functional unit and cable cabinet adopt adapter. Not only improves the reliability of the cable, and greatly facilitates the user safety and repair of cable.
6. Busbar
In order to improve the bus dynamic thermal stability and improved contact surface temperature rise, device use TMY-T2 series of hard copper, Copper plate surface will be treated with new advanced oxidation process. The performance index is superior to the traditional tin plating process.
1) Horizontal busbar
Horizontal busbar is arranged in Busbar compartment at the back of cabinet,double busbar for above 2500 A, single layer busbar for current below 2500A.Each phase is composed of 4 or 2 pcs busbar ,improve the Short circuit strength of bus.
2) Vertical bus
"L" shape hard copper tin bus is used for vertical busbar of drawer.L type bus specification(mm): (Height ×thickness)+(button×Thickness)(50 ×5)+(30 ×5)Rated current 1000A
Neutral grounding busbar
3) Adopt hard copper. Through the level of neutral grounding wire (PEN) or ground +neutral line (PE+N).
Overall and mounting dimensions(mm)
Electric power, communication cabinet installation diagram
Cabinet code |
A |
B |
C |
D |
Remark |
GCS-TG1010-4 |
1000 |
1000 |
900 |
900 |
Communication cabinet |
GCS-TG0810-4 |
800 |
1000 |
700 |
900 |
Electric power cabinet |
GCS-TG0808-4 |
800 |
800 |
700 |
700 |
Electric power cabinet |
GCS-TG0608-4 |
600 |
800 |
500 |
700 |
Electric power cabinet |
PC cabinet installation diagram
Cabinet code |
A |
B |
C |
D |
E |
F ×G |
GCS-TG1010-2 |
1000 |
1000 |
900 |
900 |
60 |
400×400 |
GCS-TG0810-2 |
800 |
1000 |
700 |
900 |
160 |
200×400 |
GCS-TG1008-2 |
1000 |
800 |
900 |
700 |
60 |
400×400 |
GCS-TG0808-2 |
800 |
800 |
700 |
700 |
160 |
200×400 |
MCC cabinet installation diagram
Cabinet code |
A |
B |
C |
D |
E |
F ×G |
GCS-TG1008-1 |
1000 |
800 |
900 |
700 |
60 |
400×350 |
GCS-TG1006-1 |
1000 |
600 |
900 |
500 |
60 |
400×350 |
GCS-TG0806-1 |
800 |
600 |
700 |
500 |
160 |
200×350 |
Main single line diagram
Program No. |
01 |
02 |
03 |
04 |
Single line diagram |
|
|
|
|
Application |
Electric power (up incoming) |
Electric power(bottom incoming) |
Electric power(Electric cable incoming) |
Communication |
|
Specification No. |
A |
B |
C |
D |
E |
F |
G |
A |
B |
C |
D |
E |
F |
G |
A |
B |
C |
D |
E |
A |
B |
C |
D |
E |
F |
G |
|
Short time withstand current/Instantaneous withstand current(kA)
|
80/176 |
|
|
|
|
80/176 |
|
|
|
|
|
|
|
|
|
|
|
|
50/105 |
50/105 |
50/105 |
50/105 |
|
|
|
|
30/63 |
|
|
|
|
30/63 |
|
30/63 |
|
|
|
|
30/63 |
Main electric components
|
Rated current(A) |
4000
|
3150
|
2500
|
2000
|
1600
|
1000
|
630 |
4000 |
3150 |
2500 |
2000 |
1600 |
1000 |
630 |
2500 |
2000 |
1600 |
1000 |
630 |
4000 |
3150 |
2500 |
2000 |
1600 |
1000 |
630 |
YCW1-4000 |
1 |
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
YCW1-3200 |
|
1 |
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
YCW1-3200 |
|
|
1 |
|
|
|
|
|
|
|
1 |
|
|
|
1 |
|
|
|
|
|
|
1 |
|
|
|
|
YCW1-2000 |
|
|
|
1 |
|
|
|
|
|
|
|
1 |
|
|
|
1 |
|
|
|
|
|
|
1 |
|
|
|
YCW1-2000 |
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
1 |
|
|
YCW1-2000 |
|
|
|
|
|
1 |
|
|
|
|
|
|
1 |
|
|
|
|
1 |
|
|
|
|
|
|
1 |
|
YCW1-2000 |
|
|
|
|
|
|
1 |
|
|
|
|
|
|
1 |
|
|
|
|
1 |
|
|
|
|
|
|
1 |
SDL-□ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(1) |
(1) |
(1) |
(1) |
(1) |
|
|
|
|
|
|
|
SDH-□□/5 |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
3(4) |
|
|
|
|
|
3 |
3 |
3 |
3 |
3 |
3 |
3 |
Cabinet width(mm) |
800(1000) |
600 |
800(1000) |
600 |
800 |
600 |
1000 |
800 |
Cabinet depth(mm) |
1000 |
800 |
1000 |
800 |
800 |
1000 |
800 |
Small compartment height usage(mm) |
|
|
|
|
Program No. |
05 |
06 |
07 |
08 |
Single line diagram |
|
|
|
|
Application |
Bus switching |
Feeder |
Dual power switch manually |
Dual power switch manually |
Main electric components
|
Specification No. |
|
A |
B |
|
A |
B |
|
|
|
A |
B |
|
|
80/176 |
|
50/105 |
|
current/Instantaneous |
|
50/105 |
50/105 |
30/63 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated current(A) |
|
4000 |
3150 |
2500 |
2500 |
2000 |
|
1000 |
630 |
|
|
YCW1-2000 |
|
|
1 |
|
|
|
|
|
|
|
|
YCW1-2000 |
|
|
|
1 |
|
|
|
1 |
|
|
|
YCW1-2000 |
|
|
|
|
1 |
|
|
|
1 |
|
|
QPS-1000 |
|
|
|
|
|
1 |
|
1 |
|
|
|
QPS-630 |
|
|
|
|
|
|
|
|
1 |
|
|
SDL-□ |
|
(1) |
(1) |
(1) |
|
|
|
|
|
|
|
SDH-□□/5 |
|
1(3) |
|
|
|
|
|
3(4) |
3(4) |
|
|
Cabinet width(mm) |
400(600) |
1000 |
1000 |
|
Cabinet depth(mm) |
400(600) |
800(1000) |
800 |
|
Small compartment height usage(mm) |
|
640 |
|
|
|
Program No. |
09 |
10 |
11 |
12 |
Single line diagram |
|
|
|
|
Application |
Dual power supply switching |
Feeder |
Feeder |
Current-limiting reactor |
|
Specification No. |
A |
B |
A |
B |
C |
D |
|
|
|
|
|
|
|
50/105 |
50/105 |
|
50/105 |
|
|
|
current/Instantaneous withstand current(kA) |
30/63 |
30/63 |
|
30/63 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Main electric components |
Rated current(A) |
400 |
250 |
630 |
400 |
250 |
160 |
400 |
250 |
100 |
|
600 |
QSA-630 |
|
|
1 |
|
|
|
|
|
|
|
|
QSA-400 |
|
|
|
1 |
|
|
|
|
|
|
|
QSA-250 |
|
|
|
|
1 |
|
|
|
|
|
|
QSA-160 |
|
|
|
|
|
1 |
|
|
|
|
|
Current-limiting reactor600A0.0084Ω/Φ |
|
|
|
|
|
|
|
|
|
|
3 |
B370, LR1, CJ35 |
1 |
|
|
|
|
|
|
|
|
|
|
B250, LR1, CJ35 |
|
1 |
|
|
|
|
|
|
|
|
|
TG-400BD, YCM1-400L, TM30 |
1 |
1 |
|
|
|
|
1 |
|
|
|
|
TG-225BD, YCM1-225M, TM30 |
|
|
|
|
|
|
|
1 |
|
|
|
TG-100BD, YCM1-100M, TM30 |
|
|
|
|
|
|
|
|
1 |
|
|
SDL-□ |
|
|
(1) |
(1) |
|
|
|
|
|
1 |
|
SDH-□□/5 |
|
|
|
|
|
|
|
|
|
|
|
Cabinet width(mm) |
800(1000) |
1000 |
800(1000) |
800 |
Cabinet depth(mm) |
600(800) |
800(1000) |
600(800) |
600 |
Small compartment height usage(mm) |
480 ×2 |
480 |
320 |
|
240(160) |
|
|
Program No. |
13 |
14 |
15 |
Single line diagram |
|
|
|
Application |
Potential transformer |
Potential transformer |
Potential transformer |
Main electric components |
Specification No. |
|
|
|
Rated current(A) |
|
|
|
QSA-63 |
|
1 |
1 |
NT00-□ |
3 |
|
|
JDG-0.5 380/100 |
2 |
2 |
1 |
JSGW-0.5 |
|
|
|
SDH-□□/5 |
|
|
|
Cabinet width(mm) |
Install in the electric power cabinet or 05 scheme Switching cabinet, connect with branch bus,Not occupy the space. |
Cabinet depth(mm) |
Small compartant height(mm) |
|
|
|
Program No. |
16 |
17 |
18 |
Single line diagram |
|
|
|
Application |
Static Var Compensator |
Static Var Compensator |
Public power |
Specification No. |
A |
B |
C |
A |
B |
C |
|
Max control motor power (kW) |
160 |
128 |
96 |
160 |
128 |
96 |
|
Main electric components |
QA-400 |
1 |
1 |
1 |
1 |
1 |
1 |
|
am-32 |
30 |
24 |
18 |
30 |
24 |
18 |
|
NT00- |
|
|
|
|
|
|
3 |
JBK3-400 |
|
|
|
|
|
|
1 |
B30C |
10 |
8 |
6 |
10 |
8 |
6 |
|
T45, LR1 |
10 |
8 |
6 |
10 |
8 |
6 |
|
BCMJ-0.4-16-3 |
10 |
8 |
6 |
10 |
8 |
6 |
|
SDH-OO/5 |
3 |
3 |
3 |
3 |
3 |
3 |
|
Cabinet width(mm) |
1000 |
800 |
1000 |
800 |
|
Cabinet depth(mm) |
800(600) |
800(600) |
|
Small compartment height usage(mm) |
|
|
|
Program No. |
19 |
20 |
21 |
22 |
Single line diagram |
|
|
|
|
|
Motor (reversible) |
Motor (reversible) |
Motor (irreversible) |
Motor (irreversible) |
Specification No. |
A |
B |
7.5 |
A |
B |
C |
A |
B |
|
Max control motor power (kW) |
37 |
15 |
|
100 |
75 |
75 |
37 |
15 |
7.5 |
Main elecric componets
|
QSA-125 |
1 |
|
|
|
|
|
|
|
|
HH17-63 |
|
1 |
3 |
|
|
|
|
|
|
NT00-□ |
|
|
|
|
|
|
|
|
|
YCM1-400L or TG-400BD, TM30 |
|
|
|
1 |
|
|
|
|
|
YCM1-225M, TM30, TG225BD |
|
|
|
|
1 |
1 |
|
|
|
YCM1-1000L or TG-100BD, TM30 |
|
|
|
|
|
|
1 |
1 |
|
NZMS4, TM30 |
|
|
|
|
|
|
|
|
1 |
B250, LC1, CJ35 |
|
|
|
1 |
|
|
|
|
|
B170-105, LC1, CJ35 |
|
|
|
|
1 |
1 |
|
|
|
B85 or LC1-D80 |
2 |
|
|
|
|
|
1 |
|
|
B45 or LC1-D32 |
|
2 |
|
|
|
|
|
1 |
|
B16 or LC1-D18 |
|
|
2 |
|
|
|
|
|
1 |
T85, LR1 |
1 |
|
|
|
|
|
1 |
|
|
TSA45, LC1 |
|
1 |
|
|
|
|
1 |
|
|
T16, LR1 |
|
|
1 |
1 |
1 |
1 |
|
|
1 |
SDL-□ |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
SDH-□□/5 |
1 |
1 |
1 |
3 |
3 |
3 |
1 |
1 |
1 |
Small compartment height usage(mm) |
320 |
160 |
160 |
480 |
320 |
320 |
160 |
Program No. |
23 |
24 |
25 |
26 |
Single line diagram |
|
|
|
|
Application |
Y-Δ Start |
Y-Δ Start |
Y-Δ Start |
Y-Δ Start |
Specification No. |
A |
B |
A |
B |
A |
B |
A |
B |
Max control motor power (kW) |
160 |
90 |
37 |
15 |
160 |
90 |
37 |
15 |
Main elecric componets
|
QSA-400~250 |
|
|
|
|
1 |
1 |
|
|
QSA-125 |
|
|
|
|
|
|
1 |
|
HH17-63 |
|
|
|
|
|
|
|
1 |
NT3-□ |
3 |
|
|
|
|
|
|
|
TG-400B |
1 |
|
|
|
|
|
|
|
YCM1-225 or TG-225D |
|
1 |
|
|
|
|
|
|
YCM1-100M or TG-100D |
|
|
1 |
1 |
|
|
|
|
B370+B250 |
2+1 |
|
|
|
2+1 |
|
|
|
B250+B170 |
|
2+1 |
|
|
|
2+1 |
|
|
B85 or LC1-D80 |
|
|
3 |
|
|
|
3 |
|
B45, TC1-D32 or 3TB44 |
|
|
|
3 |
|
|
|
3 |
T85 |
|
|
1 |
|
|
|
1 |
|
TSA45 |
|
|
|
1 |
|
|
|
1 |
T16 |
1 |
1 |
|
|
1 |
1 |
|
|
SDL-□ |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
(1) |
SDH-□□/5 |
3 |
3 |
1 |
1 |
1 |
1 |
1 |
1 |
Cabinet width(mm) |
|
|
|
|
Cabinet depth(mm) |
|
|
|
|
Small compartment height usage(mm) |
1120 |
960 |
320 |
800 |
320 |