Operating conditions

1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at - 30℃), 24h average value is not higher than +35℃; 2. Altitude: no more than 1000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: do not exceed 8 degree; 5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution; 6. No regular violent vibration; 7. Contamination grade: II class;

Technical data

Item Unit FZN25-12D/ T630-20 FZRN25-12D/ T125-20
Voltage, current parameters
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630 125
Rated short time power frequency withstand voltage (1min) kV Interrupter fracture 30; phase to earth 42; isolation fracture 48
Rated lightning impulse withstand voltage (peak) kV Phase to earth 75; isolation fracture 85
Rated peak withstand current kA 50 -
4s rated short-time withstand current kA 20 -
Rated active load breaking current A 630 -
Rated loop breaking current A 630 -
Rated cable charging breaking current A 10 -
Interrupting no load transformer capacity kVA 1250 -
Rated short-circuit breaking current kA - 31.5
Rated transfer current, rated AC current A - 2000
Fuse type SDLAJ-12 SFLAJ-12
The impactor energy output J 2-5 (medium)
Rated short-circuit closing current kA 50
Grounding switch rated stability current kA 50
Grounding switch 2S thermal stability current kA 20
The auxiliary circuit rated voltage V ≌220/110
Mechanical life Times 10000

Outline and mounting dimensions


FZN25/FZRN25-12 Indoor Vacuum Load Switch Related Video: