Selection
Operating conditions
1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at - 30℃), 24h average value is not higher than +35℃;
2. Altitude: no more than 1000m;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;
4. Earthquake intensity: do not exceed 8 degree;
5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution;
6. No regular violent vibration;
7. Contamination grade: II class;
Technical data
Item |
Unit |
FZN25-12D/ T630-20 |
FZRN25-12D/ T125-20 |
Voltage, current parameters |
Rated voltage |
kV |
12 |
Rated frequency |
Hz |
50 |
Rated current |
A |
630 |
125 |
Rated short time power frequency withstand voltage (1min) |
kV |
Interrupter fracture 30;
phase to earth 42;
isolation fracture 48 |
Rated lightning impulse withstand voltage (peak) |
kV |
Phase to earth 75;
isolation fracture 85 |
Rated peak withstand current |
kA |
50 |
- |
4s rated short-time withstand current |
kA |
20 |
- |
Rated active load breaking current |
A |
630 |
- |
Rated loop breaking current |
A |
630 |
- |
Rated cable charging breaking current |
A |
10 |
- |
Interrupting no load transformer capacity |
kVA |
1250 |
- |
Rated short-circuit breaking current |
kA |
- |
31.5 |
Rated transfer current, rated AC current |
A |
- |
2000 |
Fuse type |
|
|
SDLAJ-12 SFLAJ-12 |
The impactor energy output |
J |
|
2-5 (medium) |
Rated short-circuit closing current |
kA |
50 |
Grounding switch rated stability current |
kA |
50 |
Grounding switch 2S thermal stability current |
kA |
20 |
The auxiliary circuit rated voltage |
V |
≌220/110 |
Mechanical life |
Times |
10000 |
Outline and mounting dimensions