FZN21/FZRN21-12 Indoor Vacuum Load Switch

Selection

Operating conditions

1. Altitude: no more than 1000m; 2. The environment temperature: upper limit +40℃, lower limit -30℃; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Saturated steam pressure: daily average value is not higher than 2.2×10 -3 Mpa, monthly average is not higher than 1.8×10 -3 Mpa; 5. No severe vibration, no corrosive gas, no fire, no explosion danger place.

Technical data

Item Unit Parameter
Technical parameter of combinations
Rated voltage kV 12
Rated frequency Hz 50
The maximum rated current of the fuse A 125
Transfer current A 1550
The fuse triggered switch segment time ms 40±5
Rated short-circuit breaking current kA 31.5
Rated short-circuit closing current (prospective peak value) kA 80
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 42/49
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 75/85
Fuse impinger type Medium-sized
Technical parameters of vacuum load switch of combined electrical appliance
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630
Rated active load breaking current A 630
Rated close loop breaking current A 630
5% at rated load breaking current A 31.5
Rated cable charging breaking current A 10
Interrupting no load transformer capacity kVA 1250
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 42/48
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 75/85
4s rated short-time withstand current kA 31.5
Rated peak withstand current kA 80
Rated short-circuit closing current kA 80
Mechanical life Times 10000
Allowable cumulative thickness wear in contact mm 2
Opening and closing operating torque N·m ≤200

Overall and mounting dimensions(mm)

1. Cabinet bracket 2. Disconnector 3. Fuse 4. Insulated tension pole 5. Upper bracket 6. Vacuum interrupter 7. Static contact 8. Insulator 9. Grounding knife 10. Grounding knife spring 11. Opening spring 12. The tripping driving device 13. Insulated tension pole 14. Main axle 15. Layshaft 16. Adjusting yoke 17. Spring operating mechanism